- Programmable controller for front panel mounting
- Displaying tank level - 0...100 %, alarms for low level, high level and pump status
- 3 x SPST relay output and 1 x solid state relay
- 24 V AC/DC power supply
|
Controller HBLT-C1 built in to maintain and control refrigerant level in a pump separator.

|
Drawing
Connection diagram
Power supply
|
Environmental conditions
|
| Power supply |
24 DC + 10% |
Ambient temperature |
-20...+70 °C |
| Current consumption |
Max 600 mA |
Protection degree - front mounted |
IP45 |
| Electronic connections |
Screw terminals |
Humidity |
20…80 % |
| Wiring size |
2,5 mm2 |
Approvals |
| Input |
EMC |
EN 61000-2 |
| Analouge input - sensor |
4-20 mA |
GOST-R |
No 0903044 |
| Analouge input - feedback |
4-20 mA |
Mechanical specifications
|
| Relay function |
Alarm - max level |
Installation |
Front of panel |
| Relay voltage |
5-25 VDC |
Measure |
96 x 96 x 115 mm (W x H x D) |
| Output |
Cutting dimension in panel |
92,8 x 92,8 mm |
| Analouge output |
4-20 mA |
Materiale |
Plastic |
| Load |
3A/24VDC |
Display
|
| Relay output |
@24VAC & DC: 3 x 3A |
Display |
Red LED, 3 digits |
| @110 VAC. 3 x 5A |
Alarm |
Green and red LED |
| @240 VAC: 3 x 5A |
Programming |
From front |
| |
|
Update frequency |
1 time/sec |
| |
|
Valve position |
5 x LED |
|
| House design |
Ordering code |
| Controller - 24 V DC power supply |
HBLT-C1 |
| Controller build in a cabinet and mountet with 110/240 V power supply |
HBLT-C1-ENC |
|